TRIO-PS/1AC/24DC/2.5
102776_01_en PHOENIX CONTACT 3
Ratings / standards
Electrical Equipment for Machinery EN 60204
Safety transformers for power supply units EN 61558-2-17
Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV)
UL/C-UL recognized UL 60950
Industrial control equipment UL/C-UL Listed UL 508
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV EN 60950 (SELV)
EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents EN 61000-3-2
General data
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Installation position Horizontal DIN rail NS 35, EN 60715
Degree of protection IP20
Class of protection I, with PE connection
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Housing version Steel sheet, zinc-plated
Side element version Aluminum
Width 32 mm
Height 130 mm
Depth 115 mm
Weight 0.5 kg
Climatic data
Ambient temperature (operation) 0 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible. relative humidity (operation) 95 % (at 25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 15g in all directions in acc. with IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)