TRIO-PS/1AC/24DC/2.5
102776_01_en PHOENIX CONTACT 9
TRIO-PS/1AC/24DC/2.5
Order-No.: 2866268
Input: 100-240 V~ / 1.2-0.5 A / 50-60 Hz
Range: 85-264 V~
Output: 24 V
/2.5
A
INDUSTRIAL
CONTROL
EQUIPMENT
43KA
EN 61000-6-2
EN 61000-6-3
www.interface.phoenixcontact.com
APPROVALS
U
L
C
U
S
L
I
S
T
E
D
Read installation instructions
before connecting to mains
0 ... +70
°C (>+55
°C/+131
°F Derating)
32 ... +158
°F
-25
In
p
u
t
A
C
1
0
0-2
4
0
V
A
d
ju
s
t
22
.5
-2
9.5
V
D
C
O
K
O
u
tp
u
t
D
C
2
4
V
2
.5
A
+
+
L
N
TRIO POWER
Output
Make sure that all output lines are dimen-
sioned according to the maximum output cur-
rent or are separately protected! The cables on
the secondary side must have large cross sec-
tions in order to keep the voltage drops on the
lines as low as possible.
You can fasten the connection cables to the
housing using cable binders.
Ensure that the cable binders and the connec-
tion cables are designed for the surface tem-
peratures that occur in operation.
Make sure that the insulation of the connection
cables is not damaged when tightening the ca-
ble binders.
The connection is made using the "+" and "-" screw connections on the screw connection of the DC output. At the time of
delivery, the output voltage is 24 V DC. The output voltage can be set on the potentiometer.
Protection of the secondary side
The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is
limited to 35 V DC.
Signaling
The DC OK LED enables evaluation of the function of the power supply directly on site.
State 1 State 2
DC OK LED ON OFF
Cause Output voltage greater than
21.5 V
Output voltage less than 21.5 V or no voltage
at the output
Meaning Output voltage and output cur-
rent OK
TRIO POWER is in operation, but there is a
fault on the side of the consumer; the current
consumption is greater than I
N
or the output is
short circuited.
TRIO POWER is out of operation because
there is no mains voltage, the fuse on the pri-
mary side has been triggered, or the device is
faulty.